Features:
  • Communication function allows central monitoring
  • The 4 to 20 mA output allows communication to a central control, or as input to controls that operators monitor and adjust to maintain production
  • Panel mounting with remote display option
  • Both Under current and Over current monitoring
  • Inverter compatible from 20 to 200 Hz
  • Locked rotor protection
  • Phase imbalance protection
  • Phase loss protection
  • Thermal overload protection
  • Can be used with single-phased motors
  • Multiple operations can be linked together and monitored from one location
Unit of Measure
Items
TSBSC SHOCK RELAY FOR OVERLOAD PROTECTION

TSBSC Shock Relay for Overload Protection

TSBSC SHOCK RELAY FOR OVERLOAD PROTECTION

TSBSC Shock Relay for Overload Protection

TSBSC SHOCK RELAY FOR OVERLOAD PROTECTION

TSBSC Shock Relay for Overload Protection

TSBSC SHOCK RELAY FOR OVERLOAD PROTECTION

TSBSC Shock Relay for Overload Protection

TSBSC SHOCK RELAY FOR OVERLOAD PROTECTION

TSBSC Shock Relay for Overload Protection
Type N/A All-in One Type N/A All-in One Type N/A All-in One Type N/A Panel Mount Type N/A Panel Mount Type
Max Amperage N/A 05 N/A 30 N/A 60 N/A 100 N/A 200
Amperage Range N/A 0.15 to 6.4 A N/A 3 to 14 A N/A 10 to 60 A N/A 12 to 100 A N/A 24 to 200 A
Motor HP 230 VAC N/A 1/16 to 2 hp N/A 1 to 10 hp N/A 5 to 25 hp N/A 5 to 40 hp N/A 10 to 75 hp
Motor HP 460 VAC N/A 1/8 to 5 hp N/A 2 to 25 hp N/A 10 to 50 hp N/A 10 to 75 hp N/A 20 to 150 hp
Mounting Type N/A Panel mounting with remote display option
Electrical Life N/A Activation 100,000times at rated load cycles
Ambient Humidity N/A 30 to 85%RH (No dew condensation) %
Start Time [Min] N/A 0.2 s
Start Time [Max] N/A 12.0 s
Shock Time [Min] N/A 0.2 s
Shock Time [Max] N/A 0.5 s
Operation Frequency N/A 20 to 200 Hz
Maximum Motor Voltage N/A AC600V 50/60Hz
Operation Power N/A 100 to 240 VAC +/- 10%, 50/60 Hz
Current detection accuracy N/A +/- 5% (In case of commercial power source)
Time detection accuracy N/A +/- 5 %
Under current N/A 0.2 to 5 s
Lock when starting up N/A Set at 2 to 8 times of overcurrent setting value (OFF: No action) Trip after Star t time + 0.2s when star ting up.
Lock when operating N/A Set at 1.5 to 8 times of overcurrent setting value (OFF: No action), trip at 0.2 to 5s.
Phase-reversal N/A Trip within 0.15s, (OFF: No action)
Phase loss N/A Trip at 0.5 to 5s (OFF: No action)
Imbalance N/A Trip at 1 to 10s (OFF: No action) when setting at 10 to 50%
Alarm N/A Output when A, F and H are set (OFF: No action)
Running hour N/A Trip when 10 to 9990hr is set (OFF: No action)
Fail-safe N/A Activated when setting ON (Conducting normally: Excited, Trip: Non-excited)
Rated load N/A 3A, 250VAC
Minimum allowable load N/A DC24V, 4mA
Contact arrangement N/A OC:1c,AL/UC/TO:1a
Self-holding N/A E-r: Manual release or reset of power source, H-r: Only manual release
Auto-reset N/A A-r: Auto-reset and set the return time at 0.2s to 20min
Analog output N/A Analog output 4 to 20mA DC Output (OFF: No action) Allowable load resistance: 100O and below
Communication output N/A RS485/Modbus
Insulation between case and circuit N/A DC500V, 10MO
Dielectric strength voltage between housing-circuit N/A 2000VAC 60Hz 1min.
Dielectric strength voltage between relay contacts N/A 1000VAC 60Hz 1min.
Location N/A Indoors, where it will not get wet
Ambient temperature N/A -20 to 60 ºC
Ambient humidity N/A 30 to 85%RH (no dew condensation)
Altitude N/A 2000 m
Atmosphere N/A No corrosive gas, oil-mist or dust
Vibration N/A 5.9 m/s²
Power consumption N/A 7.0 VA
Weight N/A 0.30 kg